Cleaning schedule on an HVAC unit and the PPM checklists For HVAC.

 Cleaning Of HVAC unit and PPM of HVAC

What is HVAC?


   Hvac system is a system which is used to provide indoor air comfort by heating, ventilation and air conditioning. 
The main purpose of hvac system is to provide comfort and good quality filtered air.
HVAC air Filters 

  To provide good quality filtered air, HVAC system uses a different types of air filter in a air handler as per the area which is to be air supplied.In pharmaceuticals industries air filtration quality is very precisely maintained by using Pre filters, fine filters, HEPA filters and return air filters
  Pre filters size is varies depending on the company and criticalness of area. Which is ranging from 20 micron or 10 micron and both filters also used in one frame as Double filters. 
 Fine filters are used in Air handler after the pre filters. The micron size of fine filters are 5 micron or 3 micron. 
  After that Pre and fine filters hepa filter are used in air handler having filtration efficiency upto 99.99%. The micron size of Hepa filters are 0.3 micron and HEPA stands for High efficient particulate air.
  After Hepa Filters good quality filtered air is supplied to the required area and its again sucked by the air handler through the Return air Grills or risers from air supplied area. Return air filters are provided in return risers for more filtration efficiency. The micron size of return air filters is 10 micron. 

 Cleaning Of HVAC Air Filters 

   Air handler are continuously used for provide comfort and good quality air to the area's. Because of continuously use of air handler, its air filters are Choked. So it is required to be clean the air filters of air handler to maintain air handlers efficiency by some fixed schedule. The schedule of air filters are decided on the various aspects like ISO class of that area, uses of that area, criticalness of area and as per the company's working schedule. 
For example:- Some area's are used continuously for pharmaceuticals production, so it needed to be clean frequently to maintain the efficiency of air handler. So its schedule of filter cleaning frequency is fixed near about once in a week or once in a 2 weeks.

Important Note:- Hepa filters are not cleanable filters, it is directly replaced after its PAO test is failed.  The PAO test is taken once in a year for HEPA filters.

PPM Checklists for HVAC system 


   To keep air handler or air conditioning system in proper and continuously working conditions, we need to do its Preventive maintenance on a fixed scheduled basis like monthly or three monthly. 
  Below are the some important points that must be checked while doing a PPM of HVAC System. 

  • Check the motor bearing condition of air handler and do the greasing for motor bearings.
  • For air conditioning unit check the fan motor condition of Condenser and evaporator. 
  • In a Air handler check the Motor and blowers alignment.
  • Check the V-belt of of motor and blowers if applicable 
  • Check the vibration pads and canvas of air handler and air conditioning system  
  • Check the Condenser and evaporator finn's in air conditioning system and clean the finn's by compressed air or water.
  • Check the refrigerant pressure in the air conditioning and check its leakage of refrigerant through the system. 
  • Check the oil filter in a air conditioning system 
  • Check Compressor noise and vibration in air conditioning system and take corrective actions if needed.
  • Check the air filters condition and its gasket, clean it if required. 
  • Check the Chilled water and hot water coil leakages in the air handler. 
  • Check the air leakages throughout the Ducting systems and rectify it.
  • Clean the chilled and hot water strainer.
  • Check the electrical connections of HVAC system. 

Comments

  1. Great Post! The checklist that you’ve provided for HVAC systems is quite useful. If the HVAC systems is still showing some problems, then you must go for HVAC repair in Saskatoon.

    ReplyDelete
  2. This post is quite informative. You have provided some great information about Heating and AC systems. Daily AC Inc. provides heating and cooling in Plantation, FL at the lowest prices.

    ReplyDelete
  3. Thank you for providing this informative article. You've provided some excellent HVAC advice. Read your entire post and found it to be really interesting. Air Wave Technologies, Inc. offers low-cost HVAC repair in Anaheim.

    ReplyDelete
  4. This article is very informative. You've covered all of the essential topics about HVAC repair service, and we all know how crucial the HVAC system is in today's world. Johnson Refrigeration Inc. can provide you with affordable and efficient furnace repair in Blythe.

    ReplyDelete
  5. This is an excellent article! The information you have provided for heating and cooling system is quite helpful. If your heating system is still having issues, you should seek heating repair in Fresno.

    ReplyDelete

Post a Comment

Popular posts from this blog

How to control Temperature and Humidity in Air Handling Unit

  How to control Temperature and Humidity in Air Handling Unit Overview Air Handling unit is a system used to supply temperature and Humidity controlled filtered air to the cleanroom. For air filtration various types of filters are used in AHU. And for temperature and Humidity controlling cooling and heating coils are provided in AHU. Goals Control the temperature of air used in the cleanroom  Control the humidity of air used in cleanroom  Air filters Specifications    The air Handling unit consists of Air filter  Cooling coil Heating coil Air blower HEPA Filter  Controlling of Temperature and Humidity  By Cooling Method  The cooling coil recirculates the chilled water having temperatures between 4°C to 6°C. This chilled water comes from the Chiller through centrifugal pumps. When we start the Air Handling unit blowers sucks the air through the pre filters of the air Handling unit. When blowers sucks air, it passes through the cooling co...

AIR FLOW, AIR VELOCITY, ACPH, AHU CAPACITY

Air Changes per Hour AIR VELOCITY AND ACPH OF ROOM OR AREA   Procedure to be followed: Air Velocity Measurement and Calculation of Air Changes: Objective : To demonstrate  that the   air system is balanced and capable of delivering air velocities and providing number of air changes per hour in the respective rooms as   per requirement. Equipment to be used: Hotwire Anemometer or capture Hood Pre Requisite: Air Volumes through supply and return grills and filters should be adjusted as per the design requirement of Air Change Rate and Differential Pressure. Test Method : Ensure that the Supply blower of the AHU is "ON" prior to the start of the observations. For compliance of air change rate, velocity to be measured at 5   different locations to below the each terminal or Grill (Four Corners and center) with the help of calibrated Anemometer. Calculate the   average  velocity of the air coming from Plenum HEPA filter / supply air grill. Calculate the air...

Why ice forms at cooling coil and Suction line in Refrigeration system

 Why ice forms at cooling coil and Suction line in Refrigeration system       it's all about the relationship between a temperature and pressure and how the pressure affect the boiling point of the refrigerant. As the pressure of refrigerant increases then the temperature and boiling point also increases,  when pressure decreased temperature and boiling point also decreases. Refrigeration and air conditioning systems take use of it to cool the air or liquid.   Normal Refrigeration System      In normal refrigeration system compressor compresses the refrigerant which causes the increase in pressure and temperature of refrigerant. The hot vapour refrigerant pass through the condenser in condenser heat exchange happens and refrigerant condensate into liquid forms.Before entering in the evaporator high pressure liquid refrigerant pass through the expansion of valve. The actual device used depends on the Refrigeration system but capillary t...