Skip to main content

Why ice forms at cooling coil and Suction line in Refrigeration system

 Why ice forms at cooling coil and Suction line in Refrigeration system

      it's all about the relationship between a temperature and pressure and how the pressure affect the boiling point of the refrigerant. As the pressure of refrigerant increases then the temperature and boiling point also increases,  when pressure decreased temperature and boiling point also decreases. Refrigeration and air conditioning systems take use of it to cool the air or liquid.

  Normal Refrigeration System 



    In normal refrigeration system compressor compresses the refrigerant which causes the increase in pressure and temperature of refrigerant. The hot vapour refrigerant pass through the condenser in condenser heat exchange happens and refrigerant condensate into liquid forms.Before entering in the evaporator high pressure liquid refrigerant pass through the expansion of valve. The actual device used depends on the Refrigeration system but capillary tube is common. 
    The liquid refrigerant forced through the expansion valve, in expansion valve sudden pressure drops of liquid refrigerant. Due to pressure drop temperature and boiling points also decreases. Then in the evaporator air or liquid which to be cool absorb the heat from refrigerant. Due to heat transfer refrigerant boils into a low pressure vapour refrigerant. Refrigerant leaves the evaporator in cool vapor state and again it goes toward the compressor.
 

Low air flows over the evaporator coil

   In evaporator in air conditioning systems warm air which is to be cooled is pass through the evaporator and the refrigerant removes the heat from the warm air and supply cool air to the required area.
  But if there is a insufficient air flows through the coil can cause the low heat exchange between the air and refrigerant. Due lower heat exchange refrigerant gets too cold which causes the refrigerant evaporator condensation start to freeze over evaporator and then to the Suction line upto compressor. 

Reasons behind the low air flows over the evaporator:-
   1) A clogged filter 
   2) Unhealthy blowers fan
   3) Choked finn's of evaporator coil
   4) leakage through air ducts 
   5) Closed or blocked air vents.

Low refrigerant 

  When the refrigerant in the Refrigeration system is low that its required limit, the pressure and therefore temperature also lower in Refrigeration system. When the refrigerant is low then the temperature of the refrigerant at the start of evaporator is lower than the freezing point of water. Because the cooling or evaporator coils are so cold the moisture or water drops condensation on evaporator start to freez. Due the freezing of condensation ice start to build on over the coils which restrict the air flow through the evaporator coils. Due the the restriction of ice cubes the refrigerant can't absorb as much as heat from air moving through coils. This causes the refrigerant to boil later in the evaporator due to which ice forms over the coils and this process continues until the whole evaporator forms a block of ice. After then the refrigerant start to boil in the Suction line. This cause to drop the temperature of Suction line and which start the freezing of condensation on the Suction line upto compressor. 
   Due the ice formation lot of trouble can happens in Refrigeration system. If allowed to operate to long in this condition,Which can damages the compressor.
 

  A malfunctioning of refrigerant metering device like a bad thermal expansion valve can also cause the ice formation. 
  Conservely a bad capillary tube won't fail by passing too much Refrigerant but it might fail by passing the too little refrigerant it becomes blocked by debris or slugs of oil in the system. 

Check out similar posts below 




  

 

 

Comments

Post a Comment

Popular posts from this blog

How to control Temperature and Humidity in Air Handling Unit

  How to control Temperature and Humidity in Air Handling Unit Overview Air Handling unit is a system used to supply temperature and Humidity controlled filtered air to the cleanroom. For air filtration various types of filters are used in AHU. And for temperature and Humidity controlling cooling and heating coils are provided in AHU. Goals Control the temperature of air used in the cleanroom  Control the humidity of air used in cleanroom  Air filters Specifications    The air Handling unit consists of Air filter  Cooling coil Heating coil Air blower HEPA Filter  Controlling of Temperature and Humidity  By Cooling Method  The cooling coil recirculates the chilled water having temperatures between 4°C to 6°C. This chilled water comes from the Chiller through centrifugal pumps. When we start the Air Handling unit blowers sucks the air through the pre filters of the air Handling unit. When blowers sucks air, it passes through the cooling co...

HVAC Validation In pharma Industries

HVAC VALIDATION As per ISO guidelines for HVAC validation. In HVAC Validation  below points are determined and validated that they are in within range as per designed which will pass the respective ISO standard class acceptance criteria. 1)Air velocity and CFM calculation 2)Air changes per hour 3) Installed filter leakage test 4) HEPA filter integrity test 5)Air flow pattern test or smoke test 6)Partical count test 7)Total variable count 8) Temperatur and pressure monitoring 9) Temperature and Humidity recovery test 10) Fresh air calculation All this points are determined recorded in documents.All this validation process done by validation contractors under observation of respective company Engineer. 1) Air velocity and CFM calculation :-   - Scan the area of the HEPA filter with probe of anemometer 6 inches from the filter face. - For accurate velocity take the velocity of air at five place of filters ( Four corners and centre of filter) - Record the air velocity i...