Chiller Approach Temperature

 Chiller Approach




Chiller Approach is a essential check point for ensuring that the chiller is a running at peak efficiency.When the chiller condenser approach temperature is within operating range,it indicate the condenser tubes are clean and chiller runs efficient.When increased approach temperature reduces the efficiency and it need maintenance.

What is Approach Temperature?

Chiller Approach temperature is the temperature difference between the liquid refrigerant temperature that leaving the condenser and the leaving cooling water temperature.This temperature difference is called chiller approach temperature.

Effects of Approach Temperature:-


If the  Condenser approach temperature is within the operating range that indicate the condenser coils are in good condition and cleaned.In this condition chiller runs efficiently.
If the condenser approach temperature is out of the operating range that indicate the condenser coil scaled from inner side due to which heat transfer not done properly it needs cleaning.In this condition chiller efficiency drops.

Accepted difference condenser approach temperature range is varied as per chiller age and it's load on chiller.
For the old model chiller the difference is 
8℃ to 10℃ at full load condition.
In the newer model chiller the difference is 
2℃ to 4℃ at full load condition.

Comments

  1. But You Not mention Evaporator Approach

    ReplyDelete
    Replies
    1. Evaporator Approach is similar like Condenser Approach

      Delete
  2. sir . vapour absorption machine tharmax 460 TR chiller in 12.5 and out 12 degree Celsius in ful load .room temperature is 24 .eva in and out delta is .5 .? pls give me suggestions for improvement in the VAM.

    ReplyDelete

Post a Comment

Popular posts from this blog

How to control Temperature and Humidity in Air Handling Unit

  How to control Temperature and Humidity in Air Handling Unit Overview Air Handling unit is a system used to supply temperature and Humidity controlled filtered air to the cleanroom. For air filtration various types of filters are used in AHU. And for temperature and Humidity controlling cooling and heating coils are provided in AHU. Goals Control the temperature of air used in the cleanroom  Control the humidity of air used in cleanroom  Air filters Specifications    The air Handling unit consists of Air filter  Cooling coil Heating coil Air blower HEPA Filter  Controlling of Temperature and Humidity  By Cooling Method  The cooling coil recirculates the chilled water having temperatures between 4°C to 6°C. This chilled water comes from the Chiller through centrifugal pumps. When we start the Air Handling unit blowers sucks the air through the pre filters of the air Handling unit. When blowers sucks air, it passes through the cooling co...

HVAC Validation In pharma Industries

HVAC VALIDATION As per ISO guidelines for HVAC validation. In HVAC Validation  below points are determined and validated that they are in within range as per designed which will pass the respective ISO standard class acceptance criteria. 1)Air velocity and CFM calculation 2)Air changes per hour 3) Installed filter leakage test 4) HEPA filter integrity test 5)Air flow pattern test or smoke test 6)Partical count test 7)Total variable count 8) Temperatur and pressure monitoring 9) Temperature and Humidity recovery test 10) Fresh air calculation All this points are determined recorded in documents.All this validation process done by validation contractors under observation of respective company Engineer. 1) Air velocity and CFM calculation :-   - Scan the area of the HEPA filter with probe of anemometer 6 inches from the filter face. - For accurate velocity take the velocity of air at five place of filters ( Four corners and centre of filter) - Record the air velocity i...

Why ice forms at cooling coil and Suction line in Refrigeration system

 Why ice forms at cooling coil and Suction line in Refrigeration system       it's all about the relationship between a temperature and pressure and how the pressure affect the boiling point of the refrigerant. As the pressure of refrigerant increases then the temperature and boiling point also increases,  when pressure decreased temperature and boiling point also decreases. Refrigeration and air conditioning systems take use of it to cool the air or liquid.   Normal Refrigeration System      In normal refrigeration system compressor compresses the refrigerant which causes the increase in pressure and temperature of refrigerant. The hot vapour refrigerant pass through the condenser in condenser heat exchange happens and refrigerant condensate into liquid forms.Before entering in the evaporator high pressure liquid refrigerant pass through the expansion of valve. The actual device used depends on the Refrigeration system but capillary t...