Skip to main content

Viable Count Test, Partical Count Test in cleanroom HVAC

Partical Count Test


Viable Particle Count:-
ISO has made classifications for clean-room as it mentioned in the ISO guidelines ISO 14644-1 . As per that classification Particle count in clean room are achieved as per classification of the area.
ISO has defined 9 class standards for classification of clean rooms. In every class has it's fixed defined limit for different sizes of particle.
 
Particle count test done in two condition at REST and at OPERATION.
For particle counting particle counter Machine is used which gives the printed record of particle present in the area.This particle count test done at 4 to 5 location in one room and varies depending on the area of room.

Length of tubing used for partial counter machine should not be more than 1 meter. 

Rest condition:-
In this condition test done in a cleanroom which is not having any production activity or not any person inside the cleanroom who's doing some work.

Running Condition:-
In this  condition partical count test done while cleanroom is in running condition.

Number of sampling Points for particle Count:-
The number of sampling points in the area where particle Count should taken, is now not been calculated as per formula of square root of the surface area.

In 2015 ISO has released the new updated version of ISO 14644-1. In that version this major changes done for particle Count test.
Now the Particle Count test Sampling location taken from the ISO standard sampling location chart given below.
 
Sampling point locations can be followed as mentioned in the below table, for the large clean rooms or clean zones can be derived by equation as mentioned in the below table. 
Set up the particle counter in cleanroom or clean zone where the particle count to be measured as described in the layout. The sampling locations are evenly distributed throughout the cleanroom or clean zone.
The Sampling probe shall be positioned in the airflow at a distance of 1 to 1.5 meter from the filter or at working level and start to take readings.If the calculation results only one sample location, then consider minimum of three sample points for testing of particle count.Record the results of each sample measurement.Sampling locations related to cleanroom area as mentioned in the below table.
 

Area of cleanroom (m2) less than or equal to

Minimum number of sampling locations to be tested (NL)

2

1

4

2

6

3

8

4

10

5

24

6

28

7

32

8

36

9

52

10

56

11

64

12

68

13

72

14

76

15

104

16

108

17

116

18

148

19

156

20

192

21

232

22

276

23

352

24

436

25

636

26

1000

27

> 1000

Mentioned below Formula in the note

 
Considering area falls between two values in the table, the greater of the two should be selected.In the case of unidirectional airflow, the area may be considered as the cross section of the moving air perpendicular to the direction of the airflow. In all other cases the area may be considered as the horizontal plan area of the cleanroom or clean zone. 
Sampling location for large clean rooms or clean zones below formula will be applicable.

                                    NL = 27 x [A/1000] 

NL is the minimum number of sampling locations to be evaluated, rounded up   to the next whole number. 

A is the area of the cleanroom in m².

 Pre-Requisite: 

Tests covered in preceding sections for Air Velocity Measurement and Air Change Rate Calculation and HEPA Filter Integrity Test should be completed and results should comply with respective acceptance criteria. 

Method Applied: 

1. Set the Particulate Counter for following parameters 

Sampling Volume : 0.05 Cubic Meter 

Mode : Auto 

Cycles : 1 

Run Time : 1 minute 

Delay Time : 1 min 

Print : All Samples 

2. Particulate counting shall be carried out at predefined locations.










Comments

Popular posts from this blog

How to control Temperature and Humidity in Air Handling Unit

  How to control Temperature and Humidity in Air Handling Unit Overview Air Handling unit is a system used to supply temperature and Humidity controlled filtered air to the cleanroom. For air filtration various types of filters are used in AHU. And for temperature and Humidity controlling cooling and heating coils are provided in AHU. Goals Control the temperature of air used in the cleanroom  Control the humidity of air used in cleanroom  Air filters Specifications    The air Handling unit consists of Air filter  Cooling coil Heating coil Air blower HEPA Filter  Controlling of Temperature and Humidity  By Cooling Method  The cooling coil recirculates the chilled water having temperatures between 4°C to 6°C. This chilled water comes from the Chiller through centrifugal pumps. When we start the Air Handling unit blowers sucks the air through the pre filters of the air Handling unit. When blowers sucks air, it passes through the cooling co...

AIR FLOW, AIR VELOCITY, ACPH, AHU CAPACITY

Air Changes per Hour AIR VELOCITY AND ACPH OF ROOM OR AREA   Procedure to be followed: Air Velocity Measurement and Calculation of Air Changes: Objective : To demonstrate  that the   air system is balanced and capable of delivering air velocities and providing number of air changes per hour in the respective rooms as   per requirement. Equipment to be used: Hotwire Anemometer or capture Hood Pre Requisite: Air Volumes through supply and return grills and filters should be adjusted as per the design requirement of Air Change Rate and Differential Pressure. Test Method : Ensure that the Supply blower of the AHU is "ON" prior to the start of the observations. For compliance of air change rate, velocity to be measured at 5   different locations to below the each terminal or Grill (Four Corners and center) with the help of calibrated Anemometer. Calculate the   average  velocity of the air coming from Plenum HEPA filter / supply air grill. Calculate the air...

Why ice forms at cooling coil and Suction line in Refrigeration system

 Why ice forms at cooling coil and Suction line in Refrigeration system       it's all about the relationship between a temperature and pressure and how the pressure affect the boiling point of the refrigerant. As the pressure of refrigerant increases then the temperature and boiling point also increases,  when pressure decreased temperature and boiling point also decreases. Refrigeration and air conditioning systems take use of it to cool the air or liquid.   Normal Refrigeration System      In normal refrigeration system compressor compresses the refrigerant which causes the increase in pressure and temperature of refrigerant. The hot vapour refrigerant pass through the condenser in condenser heat exchange happens and refrigerant condensate into liquid forms.Before entering in the evaporator high pressure liquid refrigerant pass through the expansion of valve. The actual device used depends on the Refrigeration system but capillary t...